Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
186
Measurement range, R Transmitted value
0…400 dec. hex.
Resistance R
M
= (dec. value ×0.012207)
101.0 % 404,0 atDIA
Measured value out of
range
ON
32767 7FFF
100.5 % 402,0 atDIA
Measured value out of
range Off
32767 7FFF
100.0 % 400,0 Nominal value 32767 7FFF
99.997 % 399,988 32766 7FFE
… … … …
50.002 % 200,0061 16384 4000
49.998 % 199,9939 16383 3FFF
… … … …
0.003 % 0,01221 1 0001
0 % 0,0000 0 0000
Measurement range, R Transmitted value
0…800 dec. hex.
Resistance R
M
= (dec. value × 0,0244148)
101.0 % 808,0 atDIA
Measured value out of
range ON
32767 7FFF
100.5 % 804,0 atDIA
Measured value out of
range Off
32767 7FFF
100.0 % 800,0 Nominal value 32767 7FFF
99.997 % 799,976 32766 7FFE
… … … …
50.002 % 400.012 16384 4000
49.998 % 399,988 16383 3FFF
… … … …
0.003 % 0.02441 1 0001
0 % 0,0000 0 0000