203
2020/09
Extended Range value representation, 16-bit-representation
0…20 mA bipolar Diagnostics dec. hex.
Current value I
M
= (dec. value × 7.234 × 10
-4
) mA
23.70298 mA Overflow 32767 7FFF
23.51852 mA atDIA
Measured value over-
range ON
32512 7F00
23.517795 mA out of range 32511 7EFF
23,2060 mA at DIA
Measured value over-
range Off
32080 7D50
20.000723 mA 27649 6C01
20.000000 mA
nominal range
27648 6C00
10.0000 mA 13824 3600
0.0007234 mA 1 0001
0.000000 mA 0 0000
-0.1 mA Underflow atDIA
Measured value under-
range
Off
0 000×
< -0.2 mA at DIA
Measured value under-
range ON
0 000×
4…20 mA bipolar Diagnostics dec. hex.
Current value I
M
= (dec. value × 5,787 × 10
-4
) mA
22.96238 mA Overflow 32767 7FFF
22.81481 mA atDIA
Measured value over-
range
ON
32512 7F00
22.814236 mA out of range 32511 7EFF
22,56482 mA at DIA
Measured value over-
range
Off
32080 7D50
20.000579 mA 27649 6C01
20.000000 mA
nominal range
27648 6C00
12.0000 mA 13824 3600
4.0005787 mA 1 0001
4.000000 mA 0 0000
3.999421 mA out of range -1 FFFF
1.5567 mA atDIA
Measured value under-
range Off
-4222 EEBA
1.185185 -4864 ED00