4…20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value/16 × 3,907 × 10
-3
) + 4) mA
> 20.2000 mA atDIA
Measured value out of
range ON
4095 × 16 FFF×
20,1000 mA at DIA
Measured value out of
range Off
4095 × 16 FFF×
20.0000 mA
nominal range
4095 × 16 FFF×
19.9961 mA 4094 × 16 FFE×
12.0020 mA 2048 × 16 800×
4.0039 mA 1 × 16 001×
4,0000 mA 0 000×
3.7000 mA atDIA
Measured value out of
range Off
0 000×
< 3.6000 mA at DIA
Measured value out of
range ON
0 000×
3.0000 mA atDIA
Wire break Off
0 000×
< 2.9000 mA at DIA
Wire break ON
0 000×