165
2020/09
0…10 V unipolar Diagnostics dec. hex.
Voltage value U
M
= (dec. value/ 16 × 2,442 × 10
-3
) V
> 10.1000 V atDIA
Measured value out of
range ON
4095 × 16 FFF×
10,0500 V at DIA
Measured value out of
range Off
4095 × 16 FFF×
10.0000 V
nominal range
4095 × 16 FFF×
9.9976 V 4094 × 16 FFE×
5.0012 V 2048 × 16 800×
0.00244 V 1 × 16 001×
0,0000 V 0 000×
-0,0500 V atDIA
Measured value out of
range Off
0 000×
< -0.1000 V at
DIA
Measured value out
of range ON
0 000×
0…20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value/16 × 4.884 × 10
-3
) mA
> 20.2000 mA atDIA
Measured value out of
range ON
4095 × 16 FFF×
20,1000 mA at DIA
Measured value out of
range Off
4095 × 16 FFF×
20.0000 mA
nominal range
4095 × 16 FFF×
19.9951 mA 4094 × 16 FFE×
10.0024 mA 2048 × 16 800×
0.00488 mA 1 × 16 001×
0.0000 mA 0 000×
-0.1 mA underflow atDIA
Measured value out of
range Off
0 000×
< -0.2 mA at DIA
Measured value out of
range
ON
0 000×