Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
164
12-bit-representation (left-justified)
NOTE
If the measurement value representation is parameterized as ”12bit left-justified” the
diagnostic data will be transferred with the process data bits 0…3 of the respective chan-
nel.
-10…10 V bipolar Diagnostics dec. hex.
Voltage value U
M
= (dec. value/ 16 × 4,885 × 10
-3
) V
> 10.1000 V atDIA
Measured value out of
range
ON
2047 × 16 7FFF
10,0500 V atDIA
Measured value out of
range Off
2047 × 16 7FFF
10.0000 V
nominal range
2047 × 16 7FFF
9.9951 V 2046 × 16 7FE×
… … …
5.00244 V 1024 × 16 400×
… … …
0.00488 V 1 × 16 001×
0.000000 V 0 000×
-0.000488 V -1 × 16 FFF×
… … …
-5.0000 V -1024 × 16 C00×
… … …
-9.99511 V -2047 × 16 801×
-10,0000 V -2048 × 16 800×
-10,0500 V atDIA
Measured value out of
range
Off
-2048 × 16 800×
< -10.1000 V atDIA
Measured value out of
range ON
-2048 × 16 800×