163
2020/09
4…20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value × 4,883 × 10
-4
) + 4 mA
> 20.2000 mA atDIA
Measured value out of
range ON
32767 7FFF
20,1000 mA at DIA
Measured value out of
range Off
32767 7FFF
20.0000 mA
nominal range
32767 7FFF
19.9995 mA 32766 7FFE
12.00024 mA 16384 4000
4.0004883 mA 1 0001
4,0000 mA 0 0000
3.7000 mA atDIA
Measured value out of
range Off
0 0000
< 3.6000 mA atDIA
Measured value out of
range ON
0 0000
3.0000 mA atDIA
Wire break Off
0 0000
< 2.9000 mA atDIA
Wire break ON
0 0000