0…10 V unipolar Diagnostics dec. hex.
Voltage value U
M
= (dec. value × 3.052 × 10
-4
) V
> 10.1000 V atDIA
Measured value out of
range ON
32767 7FFF
10,0500 V at DIA
Measured value out of
range Off
32767 7FFF
10.0000 V
nominal range
32767 7FFF
9.9997 V 32766 7FFE
5.0002 V 16384 4000
0.000305 V 1 0001
0,000000 V 0 0000
-0,0500 V atDIA
Measured value out of
range Off
0 0000
< -0.1000 V at DIA
Measured value out of
range ON
0 0000
0…20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value × 6.104 × 10
-4
) mA
> 20.2000 mA atDIA
Measured value out of
range ON
32767 7FFF
20,1000 mA at DIA
Measured value out of
range Off
32767 7FFF
20.0000 mA
nominal range
32767 7FFF
19.9994 mA 32766 7FFE
10.0003 mA 16384 4000
0.0006104 mA 1 0001
0,0000 mA 0 0000
-0.1 mA atDIA
Measured value out of
range Off
0 0000
< -0.2 mA at DIA
Measured value out of
range
ON
0 0000