Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
152
–
Ni sensor Ni100, Ni1000 (DIN 43 760)
Ni1000TK5000
Measurement current I
meas
0…400 < 2 mA
400…4000 < 0,5 mA (integral)
Destruction limit U
max
> 30 VDC
Cutoff frequency f
G
1.5 Hz
Basic error
(nominal range at 23 °C)
0,2 % (Ni1000, Ni1000TK5000)
0,35% (Ni100)
Temperature coefficient
200 ppm/ °C
– R (resistance measurement) 0…250 , 0…400 , 0…800 0…2000 ,
0…4000
Measurement current I
meas
0…400 < 2 mA
400…4000 < 0,5 mA (integral)
Destruction limit U
max
> 30 VDC
Cutoff frequency f
G
1.5 Hz
Basic error
(nominal range at 23 °C)
0.2 %
Temperature coefficient
200 ppm/ °C
Technical data