Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
180
0…10 V bipolar Diagnostics dec. hex.
Voltage value U
M
= (dec. value × 0,001) V
11,008 V Overflow atDIA
Overflow/underflow,
OUFL ON
11008 2B0×
10,992 V at DIA
Overflow/underflow,
OUFL Off
10992 2AF×
10.512 V atDIA
Measured value out of
range ON
10512 291×
10,496 V out of range 10496 290×
10,256 V at DIA
Measured value out of
range
Off
10256 281×
10.016 V 10016 272×
10.000 V nominal range 10000 271×
…
4.992 V 4992 138×
… … …
0.016 V 16 001×
0,0000 V 0 000×
-0,05 V Underflow atDIA
Overflow/underflow,
OUFL
Off
0 000×
< -0.1 V at DIA
Overflow/underflow,
OUFL
ON
0 000×