205
2020/09
4…20 mA unipolar Diagnostics dec. hex.
Current value I
M
= (dec. value × 0,001) mA
approx. 22 mA Overcurrent at DIA Overcurrent ON 22000 55F0
21.008 mA Overflow 21008 5210
20,496 mA atDIA
Measured value over-
range
ON
20496 5010
20.016mA 20016 4E30
20.000 mA
nominal range
20000 4E20
… … …
12.000 mA 12000 2EE0
… … …
4.016 mA 4016 0FB0
4.000 mA 4000 0FA0
3.792 mA Underflow atDIA
Measured value under-
range ON
3800 0ED0
< 3.600 mA 3600 0E10
2.496 mA Wire break at DIA
Wire break ON 2496 09C0
2,000 mA 2000 07D0