249
2020/09
Output current
High level (nominal) 0.5 A
Permissible (max. for 5 minutes) 1 A
Delay at signal change and resistive load (R
LO
< 1 k)
From low to high level 50 µs
From high to low level 350 µs
Total current for all outputs Max. 4 A
Simultaneity factor 50 %
Resistive, inductive and lamp loads can be connected
UL conditions Resistive load, DC general use, Pilot Duty can be connected
Load impedance, resistive R
LO
Max. 48
Load impedance, inductive R
LI
Category DC 13 according to EN 60 947-5-1
Lamp load R
LL
< 6 W
Switching frequency
Resistive load < 100 Hz
Inductive load Category DC 13 according to EN 60 947-5-1
Lamp load < 10 Hz
Isolation voltage
Module bus/ channels 500 V
eff
Short-circuit proof According to EN 61131-2
Reset after eliminating a short circuit Automatic
Weight 65 g
Technical data

Table of Contents