291
2020/09
The default values are written in bold.
Parameters settings
Mode 0000 = voltage -10…10 V DC standard
0001 = voltage 0…10 V DC standard
0010 = voltage -10…10 VDC PA (NE 43)
0011 = voltage 0…10 VDC PA (NE 43)
0100 = voltage -10…10 VDC extended range
0101 = voltage 0…10 VDC extended range
1000 = current 0…20 mA standard
1001 = current 4…20 mA standard
1010 = current 0…20 mA PA (NE 43)
1011 = current 4…20 mA PA (NE 43)
1100 = current 0…20 mA extended range
1101 = current 4…20 mA extended range
1111 = deactivate
Data format 0 = 15 bit + sign
1 = 12 bit (left-justified)
Deactivate all diagnostics 0 = no
1 = yes
Output on module bus error 00 = substitute value
01 = keep current value
Substitute value Substitute value 0
1. The substitute value defined here will be sent in
consequence of certain events parameterized in the
gateway.
or
2. In case of a module bus error: The substitute value
defined here will be sent if the parameter ”Behavior
module bus error Ax” is set to ”output substitute
value”.
NOTE
The measurement value tables for the parameter settings ”standard”, extended range”
and ”NE 43” can be found on s. p. 300 ff.
Value representation/
resolution
range Min. value Max. value
Standard
16 bit/ 12 bit
-10…10 VDC -10 VDC 10 VDC
0…10 VDC 0 VDC 10 VDC
0…20 mA 0 mA 20 mA
4…20 mA 4 mA 20 mA
Extended range/ 16 bit/
12 bit
-10…10 VDC -11.76 VDC 11.76 VDC
0…10 VDC 0 VDC 11.76 VDC
0…20 mA 0 mA 23.52 mA
4…20 mA 0 mA 22.81 mA