12 bit representation (left-justified)
The representation of the 12 bit values corresponds to that of the 16 bit values. Only bits 0 to 3 are
set to ”0”.
dec. hex. unipolar 4…20 mA
dec. value = 1000 [1/mA] × current value [mA]
384.594 % 65535 FFFF DIA Overflow/underflow,
OUFL
ON
at 55F1…FFFF
22.000 mA
112, 506 % 22001 55F1 22.001 mA
112.500 % 22000 55F0 DIA Output value out of
range
ON
at 5209…FFFF
22.000 mA
106.256 % 21001 5209 21.001 mA
106.250 % 21000 5208 output range overrun 21.000 mA
100.006 % 20001 4E21 20.001 mA
100.000 % 20000 4E20 nominal range 20.000 mA
25.000 % 8000 1F40 8.000 mA
0.000 % 4000 0FA0 4.000 mA
-0.006 % 3999 0F9F output range underrun 3.999 mA
-1.250 % 3800 0ED8 3.800 mA
-2.500 % 3600 0E10 3.600 mA
-2.506 % 3599 0E0F DIA Output value out of
range
ON
at 0E0F…0000
3.599 mA
-12.506 % 2000 07D0 2.000 mA
-12.505 % < 1999 07CF 1.999 mA
-24.994 % 1 0001 0.001 mA
-25.000 % 0 0000 0.000 mA