35
2020/09
Test runs 7
Device with packaging, electrically tested printed-circuit board.
Electromagnetic compatibility (EMC) according to EN 50 50082-2 (Industry)
Static electricity according to EN 61 000-4-2
– Discharge through air (direct)
8 kV
– Relay discharge (indirect)
4 kV
Electromagnetic HF fields according to
EN 61 61000-4-3 and ENV 50 204
10 V/m
Conducted interferences induced by HF fields
according to EN 61000-4-6
I/O-line-length 30 m
10 V
Static electricity according to EN 61 000-4-4
Emitted interference according to EN 50 50081-2
(industry)
According to EN 55 55011 Class A, Group 1
Reliability
Pull/plug cycles of electronic modules 20
Tests (EN 61131-2)
Cold DIN IEC 68-2-1, Temperature -25 °C / 185 °F, duration
96 h; device not in use
Dry heat DIN IEC 68-2-2, Temperature +85 °C / 185 °F, duration
96 h; device not in use
Damp heat, cyclic DIN IEC 68-2-30, temperature +55 °C / 131 °F, duration
2 cycles every 12 h; device in use
Temperature change DIN IEC 68-2-14, temperature 0 to +55 °C / 32 to 131 °F,
duration 2 cycles, temperature change per minute;
device in use
Pollution severity according to IEC 664
(EN 61 61131-2)
2
Protection class according to IEC 60529 IP20 (not evaluated by UL)
NOTE
This device can cause radio disturbances in residential areas and in small industrial areas
(residential, business and trading). In this case, the operator can be required to take appro-
priate measures to suppress the disturbance at his own cost.
Technical data