Technology Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
370
LOAD_DO_
PARAM
Parameter setting of the physical output DO1
0 1: DO1 can indicate the status of different data bits as a signal. The current telegram
(byte 0) determines the data bits to which DO1 is to refer.
LOAD_ INTTIME Parameter setting of the Integration time
0 1: Bytes 0 to 1 of this process output represent a factor for defining the integration
time for frequency measurement and for determining the rotational speed.
The integration time can be adjusted between 10 ms and 10 s in 10 ms increments and is
produced by multiplying the factor × 10 ms.
With period duration measurement, this factor determines the number of periods mea-
sured in order to calculate a mean value.
A factor 1…1000 (1hex…3E8hex) is permissible.
LOAD_ UPLIMIT Parameter setting of the upper measuring limit
0 1: The value in bytes 0…3 is accepted as upper measuring limit..
LOAD_UPLIMT:
1…200 000 000 × 10
-3
Hz
1…25 000 000 × 10
-3
U/min
1…100 000 000 ms
LOAD_
LOPLIMIT
Parameter setting of the lower measuring limit
0 1: The value in bytes 0…3 is accepted as lower measuring limit..
LOAD_LOLIMIT:
0…199 999 999 x10
-3
Hz
0…24 999 999 × 10
-3
U/min
0…99 999 999 ms
Bit Description