Loading...
Technology Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
376
Parameters settings
wiring type 100000 = frequency measurement
100001 = revolutions measurement
100010 = period duration measurement
Digital input DI 0 = normal
1 = inverted
Function DI 0 = input
1 = HW gate
Lower limit 0…16 777 214 × 10
-3
Lower limit (HWORD) 0
255 (Unsigned8)
Lower limit (LWORD) 065535
upper limit 1…16 777 215 × 10
-3
Upper limit (HWORD) 0
255 (Unsigned8)
Upper limit (LWORD) 0…65535
Integration time [n*10ms] 1…1 000; 10
Sensor pulse per revolution 1…65535
Substitute value DO 1 0
1
Diagnostic DO1 0 = 1
1 = off
Function DO1 00 = output
01 = outside of limit
10 = below lower limit
11 = above upper limit
Signal evaluation (A, B) 00 = pulse and direction
01 = rotary sensor: single
Sensor/ input filter (A) 0 = 2.5 s (200 kHz)
1 = 25 s (20 kHz)
Sensor/ input filter (B) 0 = 2.5 s (200 kHz)
1 = 25 s (20 kHz)
Sensor/ input filter (DI) 0 = 2.5 s (200 kHz)
1 = 25 s (20 kHz)
sensor (A) 0 = normal
1 = inverted
Direction input (B) 0 = normal
1 = inverted
Group diagnostics 0 = release
1 = block
behavior CPU/ master stop 00 = turn off DO1
01 = proceed with operating mode
10 = DO1 switch to substitute value
11 = DO1 hold last value