Technology Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
406
Deactivate all diagnos-
tics
0 = no
1 = yes
Sending of diagnostics activated/deactivated:
This affects the separate fieldbus-specific diagnostic
message – not the diagnosis embedded in the process
input data.
Stop bits 0 = 1 Number of stop bits.
1 + 2
Parity 00 = none
01 = odd The parity bit is set so that the total number of bits (data
bits plus parity bit) set to 1 is odd.
10 = even The parity bit is set so that the total number of bits (data
bits plus parity bit) set to 1 is even.
Data bits 0 = 7 The number of data bits is 7.
1 + 8 The number of data bits is 8.
Data flow control 00 = none Data flow control is switched off.
01 = XON/XOFF Software handshake
Software handshake (XON/XOFF) is switched on.
10 = RTS/CTS Hardware handshake
Hardware handshake (RTS/CTS) is switched on.
XON character 0 - 255 (17) XON character
This character is used to start the transmission of data
from the data terminal device if the software handshake
is active.
XOFF character 0 - 255 (19) XOFF character
This character is used to stop the transmission of data
from the data terminal device if the software handshake
is active.
Parameter name Value Meaning