The maximum number of BL20-E-1SWIRE modules per BL20 station is restricted by:
the number of process data, diagnostics, parameter and configuration bytes of the BL20-E-
1SWIRE:
8 byte input data
8 byte output data
24 byte parameter data
8 byte diagnostics data.
and the field bus system used.
From version VN 01-04, BL20-E-1SWIRE can be run in conformance with the Moeller SmartWire stan-
dard. For this the ”Moeller Conformance” function has been implemented. See s. S. 458, Moeller
SWIRE conformance criteria.
Process input data
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
n -1 Data of modules to the left
n SWIRE Slave 2 SWIRE Slave 1
SC2 PKZ-ST2 SI2 SC1 PKZ-ST1 SI1
n+1 SWIRE Slave 4 SWIRE Slave 3
SC4 PKZ-ST4 SI4 SC3 PKZ-ST3 SI3
n +2 SWIRE Slave 6 SWIRE Slave 5
SC6 PKZ-ST6 SI6 SC5 PKZ-ST5 SI5
n + 3 SWIRE Slave 8 SWIRE Slave 7
SC8 PKZ-ST8 SI8 SC7 PKZ-ST7 SI7
n +4 SWIRE Slave 10 SWIRE Slave 9
SC10 PKZ-
ST10
SI10 SC9 PKZ-ST9 SI9
n +5 SWIRE Slave 12 SWIRE Slave 11
SC12 PKZ-
ST12
SI12 SC11 PKZ-
ST11
SI11
n+6 SWIRE Slave 14 SWIRE Slave 13
SC14 PKZ-
ST11
SI14 SC13 PKZ-
ST13
SI13
n+7 SWIRE Slave 16 SWIRE Slave 15
SC16 PKZ-
ST16
SI16 SC15 PKZ-
ST15
SI15
n+8 ff. Data of modules to the right