499
2020/09
The value range:
0 mV…50 mV;
0 mV…100 mV;
0 mV…500 mV;
0 mV…1000 mV;
is displayed as follows:
0000
hex
to 7FFF
hex
(decimal: 0…32767)
For the parameterization ”±50mV”:
For the parameterization ”±100mV”:
For the parameterization ”±500mV”:
For the parameterization ”±1000mV”:
voltage value = 0.001526 mV x decimal value
voltage value = 0.003052 mV x decimal value
voltage value = 0.015259 mV x decimal value
voltage value = 0.030519 mV x decimal value