527
2020/09
HART-Diagnostics Activate HART diagnostics
0 = release
1 = block
0 = no
1 = yes
Mapped channel Mapped channel VA
0 = channel 1
1 = channel 2
Mapped variable Mapped variable VA
00 = PV (1. HART variable)
01= SV (2nd HART variable)
10 = TV (3rd HART variable)
11 = QV (4th HART variable)
Channel Deactivate channel
0 = activate
1 = deactivate
0 = no
1 = yes
Short-circuit diagnosis Activate overcurrent diagnostics
0 = block
1 = release
0 = no
1 = yes
Mains suppression
0 = 50 Hz
1 = 60 Hz
Voltage mode (AI) Measurement range
0 = 0…10V
1 = -10…+10V
Voltage mode (AO) Output range
0 = 0…10 V
1 = -10…+10 V
Current range Measurement range
0 = 0…20 mA
1 = 4…20 mA
Current range Output range
0 = 0…20 mA
1 = 4…20 mA
Value representation Data format
0 = integer (15 bit + sign)
1 = 12 bit (left justified)
0 = 15 bit + sign
1 = 12 bit (left justified)
Parameters OLD Parameters NEW