15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
---------------------------------------------------------------
| | | | | | | | | | | | | | | | |
| Number of Trigger Angles that Follow (3 – 4096) | Input 1
|----------------------------------------------------------------|
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
---------------------------------------------------------------
| | | | | | | | | | | | | | | | |
| (Ignored) | Input 2
|----------------------------------------------------------------|
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
---------------------------------------------------------------
| | | | | | | | | | | | | | | | |
| First Trigger Angle (16-Bit Binary Angle) | Input 3
|----------------------------------------------------------------|
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
---------------------------------------------------------------
| | | | | | | | | | | | | | | | |
| Last Trigger Angle (16-Bit Binary Angle) | Input 3
|----------------------------------------------------------------|
You must configure the system to use the synchronization mode.
1. Use the LSYNC command to load the trigger angle table.
a. Choose the number of table entries.
b. Write the required number of words to RVP900.
Supply the angles clockwise in a strictly increasing order. They must neither reach
nor pass 0° by the table's end. The
first value may be 0.
Use binary angle representation, where Bit 15 represents 180°, Bit 14 represents 90°,
and so on.
c. Set the Ld bit command word to indicate that a new table size and set of angles are
being loaded.
d. Set a
flag bit to be set if errors are detected when loading the table of angles.
See 8.10 Get Processor Parameters (GPARM) (page 271).
Chapter 8 – Host Computer Commands
299