Examples of Event Mask Settings
To latch event #001, S1 SCR SHORT, use SPT 4 1 +L.
To disable event #128, CONFIG MODIFIED, from sounding the horn, use SPT 4 100 -A.
To enable event #012, OUT VOLT SENSE FAIL, to Dial and go into the Event Log, use SPT 4 12 +D+E.
To disable all masks for event #120, INPUT CONTACT #1, use SPT 4 120 -D-L-S-E-A.
To breakdown this syntax for the last example:
•SPT SVT command
4 — group parameter, identifying System Setting group under which the Event Mask settings reside.
120 — item parameter. In this command, that is the event ID.
-D-L-S-E-A — value parameter. In this case, the minus sign (-) disables all masks for the INPUT CONTACT #1 event.