Vertiv | Liebert® STS2/PDU
User Manual | Rev. 6 | 10/2017 127
S1 GATE DRIVE FAIL
Source 1 Gate Drive Failure
The gate drive module for an SCR for Source 1 has failed. This module is contained on the right side gate
driver board.
Press SILENCE on the touchscreen to turn off the audible alarm, if so configured. If you are accessing the
Liebert STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the
audible alarm.
Contact technical support; in the United States, call 800-543-2378. Outside the 48 contiguous United States
contact Vertiv Services, if available in your area. For international areas not covered by Vertiv Services, the
Vertiv-authorized distributor can provide technical support.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the Liebert STS2/PDU
system from a terminal, type CA and press RETURN on your keyboard.
S2 GATE DRIVE FAIL
Source 1 Gate Drive Failure
The gate drive module for an SCR for Source 2 has failed. This module is contained on the left side gate driver
board.
Press SILENCE on the touchscreen to turn off the audible alarm, if so configured. If you are accessing the
Liebert STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the
audible alarm.
Contact technical support; in the United States, call 800-543-2378. Outside the 48 contiguous United States
contact Vertiv Services, if available in your area. For international areas not covered by Vertiv Services, the
Vertiv-authorized distributor can provide technical support.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.
INTERNAL COMM FAIL
Internal CAN Communications Failed
Communications have failed in the CAN bus between the control board and the touchscreen control.
Press SILENCE on the touchscreen to turn off the audible alarm, if so configured. If you are accessing the
Liebert STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the
audible alarm.
Contact technical support; in the United States, call 800-543-2378. Outside the 48 contiguous United States
contact Vertiv Services, if available in your area. For international areas not covered by Vertiv Services, the
Vertiv-authorized distributor can provide technical support.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.