SETTING AC POWER LOSS GATE FUNCTION
Seng AC Power Loss Gate Funcon
The seng in the AC LOSS display determines what acon the operator performs during an AC power
loss. The sengs help reduce drain on the baery. You can choose between four sengs depending on
customer preferences.
Normal gate funcons connue unl the system detects a baery voltage drop below
21V. DEAD BATTERY appears on the display and the gate automacally opens. Any
push-buon CLOSE command will close the gate and any open command will re-open
the gate. If the baery connues to diminish and the system detects 18V or less, the
system iniates an automac open cycle. Any new open or close command is ignored
and the LCD appears blank. The system remains in this disabled state unl reset or
the baery recovers to 24V.
Normal gate funcons connue unl the system detects a baery voltage drop below
21V. DEAD BATTERY appears on the display and the gate automacally closes. The
gate can be opened by a special sequence of a STOP input followed by an OPEN push-
buon or directly opened with the Fire Department Open command. Any push-
buon CLOSE command will close the gate. If the baery connues to diminish and
the system detects 18V or less, the system iniates an automac open cycle. Any new
open or close command is ignored and the LCD appears blank. The system remains in
this disabled state unl reset or the baery recovers to 24V.
The operator automacally opens the gate ve seconds aer it detects an AC power
loss. The gate remains open unl AC power is restored. Any push-buon CLOSE
command will close the gate and any open command will open the gate. When the
baery voltage drops below 21V or less, the system iniates an automac open cycle.
The gate will remain open unl the baery recovers to 24V.
The operator inially does nothing aer it detects AC power loss unl it receives
an open command. Once an open command is received, the operator opens and
remains in that state. Any push-buon CLOSE command will close the gate and any
open command will open the gate. When the baery voltage drops below 21V or
less, the system iniates an automac open cycle. The gate will remain open unl the
baery recovers to 24V.
DC Solar Powered units can only be
set for AP0 or AP1.
Menu Seng Descripon
To designate what you want the operator to do during an AC power loss, access the User Menu (see “USER
MENU” on page 89) and scroll through the items unl the AP (AC LOSS) display appears.