PRIMARY AND SECONDARY MENU SETUP
Primary and Secondary Menu Setup
Determine which unit will be set up as the Primary. The other unit will be set up as the Secondary. It
doesn’t maer which unit is which, but you must idenfy the Primary and Secondary operators by taking
the following steps.
Start by conguring the PRIMARY unit:
1� At a gate status display, press the MENU buon twice. This accesses the User Menu and the CLOSE
TIMER display appears.
2� Simultaneously, press the OPEN and RESET buons to enter the Installer Menu. Release the buons
and the LEARN LIMITS display appears which is the rst item in the Installer Menu.
3� Press NEXT unl the DUAL GATE display appears. The factory default seng is 0.
4� Use the SELECT and NEXT buons to navigate and change the seng to 2 PRIMARY.
5� To exit the Installer Menu, press the MENU buon. A gate status appears in the display indicang
you have returned to Run Mode.
NOTE: For proper operaon, you must set the other gate operator as SECONDARY.
6� Move to the other Kinec operator.
7� Using the buons on the SmartDC Controller, access the DUAL GATE display through the Installer
Menu.
8� Perform the same steps, 1 through 5, but address the operator as SECONDARY, seng 1.
When the Kinec operator has been designated as the primary and the other as secondary, the dual-gate
operators will be in constant communicaon, most oen, in a peer-to-peer relaonship. For example,
• Any control input that is aached to the secondary unit will be recognized by the primary once the
Installer Menu is properly congured in both units.
• A diagnoscs log is maintained in each unit, but both units run and store the errors codes and
diagnoscs pernent to each other.
• The primary unit controls the close mer even if the mer is set in the secondary unit. If a close
mer is set in both units, the primary unit overrides the secondary seng.