8.3 Alarm Message List
8-8
0300
VERIFY ERROR
(SYSTEM CON-
FIG-DATA)
2 The setting of concurrent I/O
parameter is incorrect.
Set a correct module for the concurrent I/O
parameter in the maintenance mode.
3 An invalid value is set for the seg-
ment clock.
Set a correct value for the segment clock.
4 Inconsistency was detected in axis-
related parameters.
Correctly set the axis-related parameters.
5 Inconsistency was detected in sen-
sor parameters.
Correctly set the sensor parameters.
6 System configuration data is incon-
sistent.
• Reset the I/O module in maintenance mode.
If the error occurs again, contact your
Yaskawa representative.
The parameter is inconsistent.
7 The set optional functions are dif-
ferent from those of the mounted
optional board.
Use the functions of the mounted optional
board.
8 The function designation for the
concurrent I/O parameter is incor-
rect.
Set the correct module for the concurrent
I/O parameter in the maintenance mode.
0310
VERIFY ERROR
(CMOS MEM-
ORY SIZE)
0 The CMOS memory capacity is dif-
ferent from its initial setting.
Initialize the system or use a NIF board with
correct CMOS capacity.
0320
VERIFY ERROR
(I/O MODULE)
1 to
15
The connected I/O module is differ-
ent from the function of the set I/O
module.
Connect a correct I/O module.
16 The I/O module connected to the
PCI bus is different from the func-
tion of the set I/O module.
17
0330
VERIFY ERROR
(APPLICATION
SETTING)
0 Inconsistency was detected in the
application setting parameters.
Correctly set the application setting parame-
ters.
0340
VERIFY ERROR
(SENSOR FUNC-
TION)
0 Inconsistency was detected in the
sensor parameters.
Correctly set the sensor function.
0350
VERIFY ERROR
(DEVICENET
ALLOC FL)
0 The station No. specified by the
DeviceNet allocation file1 is incor-
rect (the station No. is out of the
allowable range, or the specified
station board is not the DeviceNet
master).
• Use the IO module setting screen in the
maintenance mode to initialize the
DeviceNet allocation file.
If the error occurs again, contact your
Yaskawa representative.
1 The MAC_ID specified by the
DeviceNet allocation file1 is not
consistent with the MAC_ID of the
specified station board.
2 Inconsistency was detected in the
scan list of the DeviceNet allocation
file1.
10 The station No. specified by the
DeviceNet allocation file2 is incor-
rect (the station No. is out of the
allowable range, or the specified
board is not the DeviceNet master).
11 The MAC_ID specified by the
DeviceNet allocation file2 is not
consistent with the MAC_ID of the
specified station board.
12 Inconsistency was found in the
scan list of the DeviceNet allocation
file2.
Alarm Message List
Alarm
Number
Message
Sub
Code
Cause Remedy