Maintenance
LITECOM, Commissioning and maintenance instructions 17.0 | 04.2024 | en 170
Complete data backup
Partial data backup
Scope of data backup
· Configuration of the LITECOM system (e.g.
system image, scenes, conditional scene
recall, presence linking)
· Device-specific settings for the DALI/eD
field devices, which are connected directly
to the LITECOM CCD and can be
configured via LITECOM (except
SEQUENCE infinity)
· DALI database for the LITECOM CCD
control device
· Configuration of the LITECOM system (e.g.
system image, scenes, conditional scene
recall, presence linking)
· Device-specific settings for the DALI/eD
field devices, which are connected directly
to the LITECOM CCD and can be
configured via LITECOM (except
SEQUENCE infinity)
· DALI database for the LITECOM CCD
control device
i
Note
If additional gateways are connected to the LITECOM CCD (e.g. LM-3DALIS), a
separate data backup must be created for each of these devices using the
service homepage in question.
· Partial data backups (if there are any)
· Log
· Password for locking against inadvertent or
unauthorised configuration
· User-defined colours
· All available images on the controls
· Time zone
· Network settings
· Activated licences
· Active API consumers
· Time zone
Area of application
After successful commissioning the
LITECOM CCD control device has to be
replaced so that the configuration can be
restored.
Before a major reconfiguration; a previous
version of the configuration can be restored if
necessary.
Table 78: Differences between data backups
i
Note
The following settings are not saved:
· Browser-specific settings, e.g. language, password to protect against inadvertent or unauthorised
operation (lock function), user settings
· Control device-specific settings
· Date and time