Using the APP Recorder 6-55
4. In the ID box enter an ID number that matches the ID number set in the data concentrator (many
times it is 1.)
5. If streaming by Ethernet select the desired protocol.
a) UDP will stream commands, configuration, and data via UDP
b) UDP_T will stream commands, and configuration via TCP and data via UDP
c) TCP will stream commands, configuration, and data via TCP
d) UDP_U will stream commands via TCP and configuration, data via UDP
In the IP box, type the IP address to where the information will be sent. Default port number for
TCP is 4712 and the default port number for UDP is 4713. Check with your IT or PMU data
concentrator administrator to ensure these are the desired ports.
IP2, if you have a second IP address you want data streamed to in parallel with the primary IP,
Check the box and enter the IP address for IP2.
Allow Any IP, If you want any IP to be able to connect to the recorder click the check box. This
will override the IP and IP2 fields.
6. If you stream information to a data concentrator that needs to connect via RS232 then check mark
RS232 box and make the appropriate settings. For the recorder, go to the Windows device
manager (Ports) to determine which com port is active. The port can change depending on the
computer type and features purchased.
7. Under What to Send, select the appropriate channels for Va, Vb, Vc, Ia, Ib, and Ic. To do this,
click the corresponding pull down menu select the desired channel.
Note: The analog channels that appear here are configured in the
Point Assignment Record.
8. The button opens the list of channels and allows you to select any or all and inserts
them. Select the channels in the correct sequence they should appear.
*CAUTION*
When Using Quick Pick to select channels You need to click the check Boxes in
the correct order. Not doing so could result in lost data.
Note: Before you select the channels, be sure that the Point Assignment Record is complete.
9. Specify the sending format by clicking the drop down menu and selecting one of the following:
If only the positive sequence voltage and positive sequence current should be streamed, select
the sending format set (V1, I1).
If the phasor for each channel should be sent with the calculated positive sequence voltage
and positive sequence current, select the sending format (Va, Vb, Vc, Ia, Ib, Ic, V1, I1).
If the phasor for each channel should be sent select (Va, Vb, Vc, Ia, Ib, Ic)
If the phasor for each channel should be sent with the calculated positive sequence voltage
and positive sequence current, the negative sequence voltage and negative sequence current,
and the zero sequence voltage and zero sequence current select the sending format (Va, Vb,
Vc, Ia, Ib, Ic, V1, I1, V2, I2, V0, I0).
If the phasor for all channels in the DFR should be sent, select the sending format All Analog
Channels.