3.4 Operation and setting via AUMA COM-AC programming software
Data from the actuator can easily be imported, exported and settings
changed and saved using the AUMA COM-AC programming software
(option) in combination with a computer.
Depending on the version, the connection between computer and AUMATIC
can be performed with cable (infra-red interface) or without cable (Bluetooth
interface) (not included in these instructions) .
3.4.1 Operation setting via COM-AC
The COM-AC software can transmit the operation commands OPEN, STOP,
CLOSE to the actuator.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
COM-AC CONTROL (M1P0)
LOCAL CLIENT (M1P10)
Default value: REMOTE AND LOCAL
Description of the parameter settings:
REMOTE AND LOCAL
The actuator can be operated in selector switch position LOCAL CONTROL
or REMOTE CONTROL via the COM-AC with the OPEN, STOP, CLOSE
commands.
LOCAL CONTROL ONLY
The actuator can be operated in selector switch position LOCAL CONTROL via
the COM-AC with the OPEN, STOP, CLOSE commands.
No operation control is possible in selector switch position REMOTE CONTROL.
12
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Profibus DP Manual
3
1 2
Figure 5
1 Infra-red interface 2 Bluetooth interface (option)
3 Bluetooth LED
EDIT M1P10
LOCAL CLIENT
REMOTE AND LOCAL
:EDIT ¿:OK C:ESC