7.6.7 Source of setpoint E1: view
This value is set in the factory and can only be changed by the AUMA ser
-
vice.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SETUP (M41)
SETPOINT E1 (M4100)
Default value: DP
È
Description of the parameter settings:
NONE
There is no setpoint source available.
LOGIC ANALOG IN1
For AUMA service only (the setpoint E1 is transmitted from external via the
analogue input 1 directly to the logic board.
I/O1 ANALOG IN1
The setpoint E1 is transmitted via the I/O interface board, analogue input 1.
I/O1 ANALOG IN2
The setpoint E1 is transmitted via the I/O interface board, analogue input 2.
DP
The setpoint E1 is transmitted via the Profibus DP interface board, channel
1 or channel 2.
DP1 ANALOG IN1
The setpoint E1 is transmitted via the Profibus DP interface board, analogue
input 1.
DP1 ANALOG IN2
The setpoint E1 is transmitted via the Profibus DP interface board, analogue
input 2.
DP2 ANALOG IN1
The setpoint E1 is transmitted via the second Profibus DP interface board,
analogue input 1.
DP2 ANALOG IN2
The setpoint E1 is transmitted via the second Profibus DP interface board,
analogue input 2.
59
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Profibus DP
VIEW
SETPOINT E1
DP
C:ESC