7.16.3 Monitoring of the max. number of starts per hour and max. running time per hour
The AUMATIC monitors any exceeding of
.
the maximum number of starts (motor starts) per hour
.
the maximum running time (on-time) per hour.
If any of these values has been exceeded, the actuator will however not be
stopped, b
ut the following warning signals are sent:
.
Status indication S0 : operation mode OFF/LOCAL = WRN+NR
.
Status indication S0/S6: operation mode REMOTE = WARNING
.
Status indication S2: WARNING STARTS/RUN
The warning signals will automatically be cleared if the number of starts per
second and the set max. running time per hour are no longer reached.
An exceeding is also logged in the operating data counters
WRN.STARTS/RUN1 and WRN.STARTS/RUN2 (page 95).
WRN.STARTS/RUN1 contains the total of all starts/running time warnings.
WRN.STARTS/RUN2 contains the max. time duration of a starts/running
time warning.
Example:
The AUMATIC signals a total of 3 starts/running time warnings because of
an exceeding of the set cycles/h or running time/h: once 20 min., once 15
min, once 22 min. Afterwards the operating data counters contain the follow-
ing values:
WRN.STARTS/RUN1 = 57 min. = total of all time sections (20+15+22 min)
WRN.STARTS/RUN2 = 22 min. = longest time section
Switching on/off the monitoring of the max. number of starts and the
max. running time
To be able to view settings or to perform modifications, the
MONITORING
parameter must be set to FUNCTION ACTIVE.
Information This parameter is also used to switch the operating time monitoring
(page 88) on or off.
Æ
Via the menu to parameter:
MAIN MENU (M0)
CONFIGURATION (M4)
SPECIAL FUNCTIONS (M40)
MONITOR TRIGGERS (M4016)
Default value: FUNCTION ACTIVE
È
Description of the parameter settings:
FUNCTION NOT ACTIVE
The MAX STARTS/HOUR and MAX DUTY CYCLE parameters are not
shown in the display.
FUNCTION ACTIVE
The MAX STARTS/HOUR and MAX DUTY CYCLE parameters are shown in
the display.
86
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Profibus DP Manual
EDIT M4016
MONITOR TRIGGERS
FUNCTION ACTIVE
:EDIT ¿:OK C:ESC