8.2.2 Diagnostic indications (D) via the display
The information contained in the diagnostic indications is only provided for
the AUMA service and for enquiries in the factory.
1. Change from the status indications (group
S) to the diagnostic indica
-
tions (group
D): Press C push button and hold it down until the group D0
appears (menu M is hereby skipped).
2. To return to the status indications:
Press
C push button briefly once.
Wiring of the end position inputs (D0)
È
Description of the displays:
PULL DOWN INPUTS
Pull Down resistors are used for the inputs of the end position signals (limit
and torque switches) on the logic board.
PULL UP INPUTS
Pull Up resistors are used for the inputs of the end position signals (limit and
torque switches) on the logic board.
Actuator signals (D1)
È
Description of the displays:
NO SIGNALS
No actuator signals set
TSC (DSR)
Torque signal CLOSED tripped in actuator (not stored)
TSO (DOEL)
Torque signal OPEN tripped in actuator (not stored)
LSC (WSR)
Limit switching CLOSED tripped in actuator
LSO (WOEL)
Limit switching OPEN tripped in actuator
THERMAL FAULT
Motor protection tripped. Remedy:
Wait for cool-down; the signal is then either cancelled automatically or if not,
bring selector switch to position Local and operate Reset push button.
Check fuse F4.
97
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Profibus DP
ENDPOS. INPUTS D0
PULL DOWN INPUTS
ACTUATOR SIGNALS D1
NO SIGNALS