FAIL CLOSE
The actuator runs to end position CLOSED.
FAIL OPEN
The actuator runs to end position OPEN.
FAIL TO PRESET
The actuator runs to the predetermined position.
6.5.4 Preset position definition
If the
FAILURE TO PRESET failure action(FAILURE POSITION param-
eter) is set, the actuator runs to the preset position stated here.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
FAILURE BEHAVIOUR (M15)
PRESET POSITION (M1513)
Default value: 0.0 %
Setting range: from 0.0 % to 100.0 % (from OPEN to CLOSED)
6.5.5 Failure delay time setting
Determines the time elapsed between the recognition of a cable break and
the initiation of the failure action.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
FAILURE BEHAVIOUR (M15)
DELAY TIME (M1511)
Default value: 3.0 s
Setting range:
0.0 to 1200.0 seconds (20 min.)
43
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Profibus DP
EDIT M1513
PRESET POSITION
0.0 %
:EDIT ¿:OK C:ESC
EDIT M1511
DELAY TIME
3.0 s
:EDIT ¿:OK C:ESC