7.7.7 Internal process setpoint setting
If necessary, the process controller can also be operated without external
process setpoint. An internal process setpoint may be set with this parame
-
ter.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
PROCESS CONTROL PID (M1I)
INTERNAL SET POINT (M1I14)
Default value: 0%
Setting range: 0 to 100 %
Information The actuator only reacts to the preset internal setpoint if the PID TYPE
parameter is set to PID-INTERN.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
PROCESS CONTROL PID (M1I)
PID TYPE (M1I1C)
Default value: PID-EXTERN
È
Description of the parameter settings:
PID-INTERN
Process control via internal process setpoint
PID-EXTERN
Process control via external process setpoint
65
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Profibus DP
EDIT M1I1C
PID TYPE
PID-EXTERN
:EDIT ¿:OK C:ESC
EDIT M1I14
INTERNAL SET POINT
0%
:EDIT ¿:OK C:ESC