7.7 Process controller (option)
Figure 10 shows the function of the process controller:
The process controller (2) receives the process setpoint (E1) and the process
variable (E4) (e.g. from a sensor). On the basis of both values, the process
controller calculates the position setpoint (E7) for the positioner (3).
In turn, the positioner (3) compares this setpoint with the position feedback
(E2) of the valve and issues the operation commands (OPEN - CLOSE) to
the actuator.
Table of contents:
7.7.1 Setting procedure
7.7.2 Process controller activation
7.7.3 Proportional amplification Kp setting
7.7.4 Reset time Ti setting
7.7.5 Rate time Td setting
7.7.6 Derivative gain Kd setting
7.7.7 Internal process setpoint setting
7.7.8 Behaviour on loss of the process setpoint (wire break monitoring)
7.7.9 Inverse operation setting
7.7.10 Travel limitation
7.7.11 Reaction monitoring setting
7.7.12 Input range of process setpoint E1: view
7.7.13 Input range of process variable E4: view
61
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Profibus DP
E1
E4
2
E2
6
7
4
1
3
5
E7
Figure 10
1 AUMATIC controls 7 Valve
2 Process controller
3 Positioner E1 Process setpoint
4 Actuator E2 Position feedback
5 Positioner e.g. RWG/MWG E4 Process variable
6 Sensor E7 Position setpoint (internal)

Table of Contents

Other manuals for AUMA Aumatic AC 01.1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA Aumatic AC 01.1 and is the answer not in the manual?

AUMA Aumatic AC 01.1 Specifications

General IconGeneral
BrandAUMA
ModelAumatic AC 01.1
CategoryControl Unit
LanguageEnglish

Related product manuals