6.4.4 EMERGENCY position definition
If the EMERGENCY operation action
FAIL TO PRESET (EMERGENCY
POSITION
parameter) is set, the actuator runs to the EMERGENCY
position stated here.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
EMERGENCY BEHAVIOUR (M16)
PRESET POSITION (M1614)
Default value: 0,0 %
Setting range: from 0.0 % to 100.0 % (from OPEN to CLOSED)
6.4.5 Motor protection and/or torque switching: by-pass
During the EMERGENCY operation, the motor protection and/or torque
switching can be by-passed.
This value is set in the factory and can only be changed by authorised
AUMA staff.
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
EMERGENCY BEHAVIOUR (M16)
EMERGENCY BY-PASS (M1603)
Default value: NONE
È
Description of the parameter settings:
NONE
No by-pass of motor protection.
THERMAL
The signals of the thermoswitches or the PTC thermistors of the motor
winding are by-passed.
TORQUE
The signals of the torque switching in the actuator (TSC (DSR)/TSO
(DOEL)) are by-passed
THERMAL AND TORQUE
The signals of the thermoswitches or PTC thermistors and the signals of the
torque switching are by-passed.
Information For actuators with explosion protection, the motor protection and the torque
switching cannot be by-passed.
40
Actuator controls
AUMATIC AC 01.1/ACExC 01.1 Profibus DP Manual
EDIT M1614
PRESET POSITION
0.0%
:EDIT ¿:OK C:ESC
EDIT M1603
EMERGENCY BY-PASS
NONE
C:ESC