Setting the max. permissible number of starts
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
MONITOR TRIGGERS (M18)
MAX STARTS/HOUR (M1810)
Default value: 1200
Setting range: 0 to 1800 starts (motor starts)
Setting the max. permissible running time
Æ
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
MONITOR TRIGGERS (M18)
MAX DUTY CYCLE (M1811)
Default value: 15 MIN
È
Description of the parameter settings:
15 MIN
The max. permissible running time (on-time) per hour amounts to 15 min.
24 MIN
The max. permissible running time (on-time) per hour amounts to 24 min.
30 MIN
The max. permissible running time (on-time) per hour amounts to 30 min.
87
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Profibus DP
EDIT M1810
MAX STARTS/HOUR
1200
:EDIT ¿:OK C:ESC
EDIT M1811
MAX DUTY CYCLE
15 min
:EDIT ¿:OK C:ESC