Description of the parameter settings:
NOT USED
No signal.
C___POS¯¯¯¯¯O
Signal active from reaching the intermediate position to end position OPEN.
C¯¯¯¯¯POS___O
Signal active from end position CLOSED to reaching the intermediate posi-
tion.
C___POS___O
Impulse signal issued when going through intermediate position
Figure 8 shows the signal behaviour in intermediate positions.
Further feedback signals which can be used together with the multiport
valve function (option):
Description of the parameter settings:
SETPOINT REACHED
As each intermediate position is processed as a setpoint, the signal
SETPOINT REACHED is issued after reaching any intermediate position.
ACTUATOR MOVING
Is signalled as long as the actuator is still running to the intermediate posi-
tion and no intermediate position signal has been issued yet.
51
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Profibus DP
0
1
0
1
0
1
0
1
POS
A
B
C
D
Figure 8
A NOT USED 1 Active signal
BC
___POS¯¯¯¯¯¯O 2 Signal not activated
C C¯¯¯¯¯¯POS
___O
DC
___POS___O POS = intermediate position