Ò
Set the running time (
MONITOR TRIGGERS parameter) in accordance
with the actual running time.
Ò
Check tripping behaviour of end position switches.
Ò
Check actuator mechanics.
WARNING STARTS/RUN
The preset values for max. starts/h or max. running time/h have been
exceeded.
Ò Chec
k modulating behaviour.
Ò Increase dead time.
Ò Reduce number of setpoint changes.
INTERNAL FEEDBACK
Position transmitter (potentiometer or RWG) is not standardised.
Ò Oper
ate actuator into both end positions (OPEN and CLOSED), one
after the other.
INTERNAL WARNING
Internal warnings have occurred.
For further information:
1. Go to group
D0: Press C and hold down until the D0 diagnostic indica-
tion is displayed.
2. Go to diagnostic indication
D3 : Press q three times.
FEEDBACK E2 LOSS
Signal loss of position transmitter.
Ò Chec
k position transmitter signal.
1. Go to group
D0: Press C and hold down until the diagnostic indication
D0 is displayed.
2. Go to diagnostic indications
D7,D8, or D9 . Press q either seven, eight,
or nine times.
Ò Check position transmitter wiring (potentiometer or RWG).
Ò Check
POSITION E2 parameter. The setting must correspond to the
wiring diagram.
SETPOINT E1 LOSS
Signal loss of the setpoint.
Ò Chec
k wiring.
TORQUE E6 LOSS
Signal loss of torque source.
Ò Chec
k wiring.
I/O1 ANALOG IN1 LOSS
Signal loss of parallel interface of analogue input 1(only for fieldbus/stan-
dard interface combinations, page 83).
Ò Chec
k wiring.
I/O1 ANALOG IN2 LOSS
Signal loss of parallel interface of analogue input 2 (only for fieldbus/stan-
dard interface combinations, page 83).
Ò Chec
k wiring.
P-FEEDBACK E4 LOSS
Signal loss of process feedback E4 (only if process controller is available
and active).
Ò Chec
k wiring.
FIBRE OPTIC LOSS
Signal loss of fibre optic cable (only for bus with fibre optic loop topology).
Ò
Chec
k wiring.
ANALOG IN1 BUS1 LOSS
Signal loss of analogue input 1.
Ò
Chec
k wiring.
ANALOG IN2 BUS1 LOSS
Signal loss of analogue input 2.
Ò
Chec
k wiring.
93
Actuator controls
Manual AUMATIC AC 01.1/ACExC 01.1 Profibus DP

Table of Contents

Other manuals for AUMA Aumatic AC 01.1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA Aumatic AC 01.1 and is the answer not in the manual?

AUMA Aumatic AC 01.1 Specifications

General IconGeneral
BrandAUMA
ModelAumatic AC 01.1
CategoryControl Unit
LanguageEnglish

Related product manuals