Note
“U”and“%FS”usedinthe“FactorySetting”and“Setting”columnsin
thetablemeanthefollowing:
U: Thedecimalpointchangesaccordingtotheinputrangetype
setting.Forexample,whenonedigitpastthedecimalpointis
allowed,-1999Ubecomes199.9,and9999Ubecomes999.9.
%FS: Thenumbersanddecimalpointpositionchangesaccordingto
theinputrangesetting.
Forexample,whentheinputrangeis0.0to800.0°C,0%FSis0.0
and100%FSis800.0.
Variable parameter settings
P
A
R
A
No. Item Code Item
Factory
Setting
User
Setting
Setting
1
L
O
C
Key lock 0 0: Key lock disabled
1: Display of setup data settings disabled
2: Display of parameter settings and
program settings disabled
3: Use of operation keys disabled
4: Display of parameter settings and
program settings displayed, and use of
operation keys disabled
[Note]
Two or more key lock setting values
for actual key lock items and items
assigned to
PARA
can be displayed and
set.
2
P
R
T
C
Program protect 0 0: Changing program settings enabled
1: Changing program settings disabled
3
F
L
Input 1 digital lter 0.0 0.0 to 120.0s
[Note]
0.0 disables the lter.
4
P
B
1
Input 1 bias 0U -1000 to +1000U
5
S
B
1
SP1 bias 0U -1999 to +9999U
[Note]
SP bias is commonly eective in all
programs and all segments.
6
O
T
L
MV change limitter
(CH1)
0.0 0.0 to 10.0% (0.1%s steps)
[Note]
0.0 disables the limit.
7-8
Chapter 7. PARAMETER SETUP
7 - 3 Parameter Setup List

Table of Contents