Note
“U”and“%FS”usedinthe“FactorySetting”and“Setting”columnsin
thetablemeanthefollowing:
U: Thedecimalpointchangesaccordingtotheinputrangetype
setting.Forexample,whenonedigitpastthedecimalpointis
allowed,-1999Ubecomes199.9,and9999Ubecomes999.9.
%FS: Thenumbersanddecimalpointpositionchangesaccordingto
theinputrangesetting.
 Forexample,whentheinputrangeis0.0to800.0°C,0%FSis0.0
and100%FSis800.0.
 
Variable parameter settings “
P
 
A
 
R
 
A
”
No. Item Code Item
Factory 
Setting
User 
Setting
Setting
1
L
 
O
 
C
Key lock 0 0:  Key lock disabled
1:   Display of setup data settings disabled
2:   Display of parameter settings and 
program settings disabled
3:  Use of operation keys disabled
4:   Display of parameter settings and 
program settings displayed, and use of 
operation keys disabled
[Note]
   Two or more key lock setting values 
for actual key lock items and items 
assigned to 
PARA
 can be displayed and 
set.
2
P
 
R
 
T
 
C
Program protect 0 0:   Changing program settings enabled
1:   Changing program settings disabled
3
F
 
L
Input 1 digital lter 0.0 0.0 to 120.0s
[Note]
  0.0 disables the lter.
4
P
 
B
 
1
Input 1 bias 0U -1000 to +1000U
5
S
 
B
 
1
SP1 bias 0U -1999 to +9999U
[Note]
   SP bias is commonly eective in all 
programs and all segments.
6
O
 
T
 
L
MV change limitter 
(CH1)
0.0 0.0 to 10.0% (0.1%s steps)
[Note]
  0.0 disables the limit.
7-8
Chapter 7. PARAMETER SETUP
7 - 3  Parameter Setup List