9-10
Chapter 9. MAINTENANCE & TROUBLESHOOTING
G.Soak items cannot be displayed by repeatedly pressing in
program setup state
Cause Remedy
Programming items are set to “display
OFF”.
Set setup data
C
7
0
setting to 0.
PV start items, cycle items and pattern link items cannot be displayed
by repeatedly pressing in program setup state
Cause Remedy
Programming items are set to “display
OFF”.
Set setup data
C
7
1
setting to 0.
Insertion/deletion of segments cannot be confirmed by pressing
FUNC
+
ENT
in program setup state
Cause Remedy
The program setup cannot be changed. Set program parameter
P
R
T
C
setting to 0.
The program being set up is being oper-
ated (RUN. HOLD, FAST, END).
Reset the controller.
Not pattern item on programming map Move to pattern item on programming map.
Pattern item of non-set segment on pro-
gramming map
Either move to already set up segment, or set up
segment.
Program deletion cannot be confirmed by pressing
FUNC
+
CLR
while en-
tering pattern items in program setup state
Cause Remedy
The program being set up is being oper-
ated (RUN. HOLD, FAST, END).
Reset the controller.