7-12
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory
Setting
User
Setting
Setting
31
.-c
l
Motor valve open-
ing adjustment fully
closed position
1000 0 to (fully open adjustment - 500)
[Note]
On models other than 2G output mod-
els, “– – – –” is displayed and setting is
not possible.
On 2G output models, when
.-C
setting is 2, “– – – –”is displayed and
setting is not possible.
32
.-O
p
Motor valve open-
ing adjustment fully
open position
9000 (fully closed adjustment + 500) to 9999
[Note]
On models other than 2G output mod-
els, “– – – –” is displayed and setting is
not possible.
On 2G output models, when
.-C
setting is 2, “– – – –” is displayed and
setting is not possible.
33
.-t
Motor valve open-
ing adjustment fully
open/closed time
30.0 5.0 to 240.0s
[Note]
On models other than 2G output mod-
els, “– – – –” is displayed and setting is
not possible.
Description of variable parameter settings
L
O
C
(key lock)
0: Keylockdisabled
1: Displayofsetupdatasettingsdisabled
2: Displayofparametersettingsandprogramsettingsdisabled
3: Useofoperationkeysdisabled
4: Displayofparametersettingsandprogramsettingsdisplayed,
anduseofoperationkeysdisabled
•When
LOC
issetto1,thefollowingkeysaredisabled.
Basicdisplaystate:
FUNC
+
CLR
+
DISP
(generalreset)
O n l y
SET
canbeselectedbysettinggroupselectionintheparam-
etersetupstate.
•When
LOC
issetto2,thefollowingkeysaredisabled.
Basicdisplaystate:
FUNC
+
PROG
(programsetup)
+
PROG
(programcopy)
FUNC
+
CLR
+
DISP
(generalreset)
O n l y
PARA
canbeselectedbysettinggroupselectioninthe
parametersetupstate.
However,notethatitemsassignedto
PARA
canbecalledupby
PARA
inthebasicdisplaystate.