Optionalauxiliaryoutputscanbeaddedon.
WARNING
Before removing, mounting, or wiring the DCP31, be sure to turn off the power to
the DCP31 and all connected devices.
Failure to do so might cause electric shock.
0D, 5G, 6D auxiliary outputs
Handling Precautions
• 4 to 20mAdc and 0 to 20mAdc can be selected in setup data
C
9
0
.
• Use shielded cable only.
2G, 3D, 5K auxiliary outputs
Auxiliaryoutput1isnotprovidedfor2G,3Dand5Koutputs.
Handling Precautions
• 4 to 20mAdc and 0 to 20mAdc can be selected in setup data
C
9
0
.
• Use shielded cable only.
14
15
16
17
18
19
Receiver
Receiver
Auxiliary output 1
(output 2)
4 to 20/0 to 20 mAdc
Resistive load 600 Ω max.
Auxiliary output 2
(output 3)
4 to 20/0 to 20 mAdc
Resistive load 600 Ω max.
17
18
19
Receiver
Auxiliary output 2
(output 3)
4 to 20/0 to 20 mAdc
Resistive load 600 Ω max.
4-12
Chapter 4. WIRING
4 - 9
Connecting auxiliary outputs (outputs 2, 3)