EasyManua.ls Logo

Azbil DCP31 - 4 - 9 Connecting auxiliary outputs (outputs 2, 3)

Azbil DCP31
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Optionalauxiliaryoutputscanbeaddedon.
WARNING
Before removing, mounting, or wiring the DCP31, be sure to turn off the power to
the DCP31 and all connected devices.
Failure to do so might cause electric shock.
0D, 5G, 6D auxiliary outputs
Handling Precautions
• 4 to 20mAdc and 0 to 20mAdc can be selected in setup data
C
9
0
.
• Use shielded cable only.
2G, 3D, 5K auxiliary outputs
Auxiliaryoutput1isnotprovidedfor2G,3Dand5Koutputs.
Handling Precautions
• 4 to 20mAdc and 0 to 20mAdc can be selected in setup data
C
9
0
.
• Use shielded cable only.
14
15
16
17
18
19
Receiver
Receiver
Auxiliary output 1
(output 2)
4 to 20/0 to 20 mAdc
Resistive load 600 Ω max.
Auxiliary output 2
(output 3)
4 to 20/0 to 20 mAdc
Resistive load 600 Ω max.
17
18
19
Receiver
Auxiliary output 2
(output 3)
4 to 20/0 to 20 mAdc
Resistive load 600 Ω max.
4-12
Chapter 4. WIRING
4 - 9
Connecting auxiliary outputs (outputs 2, 3)

Table of Contents