The program No. does not change by pressing 
PROG
 in basic display state
Cause Remedy
Program selection by external switch input not 0. Set all external switch inputs RSW8 to 12 OFF.
The controller is not in the READY mode. Reset the controller.
The controller is in the constant-value operation 
mode.
Set constant-value operation data 
 
.O
 
D
 
E
 setting to 0.
Key lock is enabled. Set variable parameter 
L
 
O
 
C
 setting to 0 to 2.
 
The program No. does not change by pressing   in the basic display 
state
Cause Remedy
Program selection by external switch input not 0 Set all external switch inputs RSW8 to 12 OFF.
The controller is not in the READY mode. Reset the controller.
The controller is in the constant-value operation 
mode.
Set constant-value operation data 
 
.O
 
D
 
E
 setting to 0.
Entry changeable display state by 
   in 
MANUAL mode
Press 
DISP
 .
Key lock is enabled. Set variable parameter 
L
 
O
 
C
 setting to 0 to 2.
 
The controller does not change to RUN mode by pressing 
RUN/HOLD
 in the 
basic display state
Cause Remedy
The currently selected program in READY mode 
has not been set up.
Select an already set up program.
The controller is in the END mode. Reset the controller to READY mode.
Key lock is enabled. Set variable parameter 
L
 
O
 
C
 setting to 0 to 2.
 
The controller does not change to HOLD mode by pressing 
RUN/HOLD
 in the 
basic display state
Cause Remedy
The controller is in the READY or FAST mode. RUN mode is entered from READY or FAST mode. Press 
RUN/HOLD
 key again.
The controller is in the END mode.
Reset the controller to READY mode, and press 
RUN/HOLD
 
twice.
The controller is in the constant-value operation 
mode.
Set constant-value operation data 
 
.O
 
D
 
E
 setting to 0.
Key lock is enabled. Set variable parameter 
L
 
O
 
C
 setting to 0 to 2.
9-5
Chapter 9. MAINTENANCE & TROUBLESHOOTING
9 - 3  Trouble during Key Entry