8-8
Chapter 8. PROGRAM SETUP
Display
“----”isdisplayedfortheSPandtimesettingvaluesinnon-set
segments.
Setting up events 1 to 3 items
When event type is PV type event
(1) Inthesettingdisplaystate,movetotheevent1to3itemsofthe
segmenttobesetupontheprogrammingmap.
(2) Ifyoupress
ENT
,theupperdisplaystartsblinkingtoindicate
startofentrytotheNo.1setup.
(3) Press
, , or tosettotheNo.1setupevent
operatingpointsetting.
Settingrange: -1999to+9999U
0to9999U(incaseofabsolutevaluedeviation
event)
-10.0to+110.0%(incaseofMV,MFBevent)
(4) Whenyoupress
ENT
,blinkingontheupperdisplaystops.
(When
FUNC
+
CLR
arepressed,theupperdisplayreturnsto
“----”andstopsblinking.)
Display (PV type event)
•“----”isdisplayedforthesettingvaluesinnon-setsegments.
•Whensetupdata
C68
issetto1,event1to3itemsonthepro-
grammingmapareskippedandnotdisplayed.
SP
TM
SP1 setting value
Time setting value
Program No. Segment No.
Pattern
tendency
EV1 to EV3 and T1 to T5 all out
Operating point setting value
Program No. Segment No.
Pattern
tendency
LEDs corresponding to EV1 to EV3 lit. T1 to T5 all out