Resistance temperature detector (RTD)
Input Format Range No. Code Temp. Range (°C) Temp. Range (°F)
JIS' 89 Pt100
(IEC Pt100Ω)
32 F50 -200.0 to +500.0 -300 to +900
33 F46 -200.0 to +200.0 -300 to +400
34 F32 -100.0 to +150.0 -150.0 to +300.0
35 F36 -50.0 to +200.0 -50.0 to +400.0
36 F38 -60.0 to +40.0 -76.0 to +104.0
37 F33 -40.0 to +60.0 -40.0 to +140.0
38 F05 0.0 to 500.0 0.0 to 900.0
39 F03 0.0 to 300.0 0.0 to 500.0
40 F01 0.00 to 100.00 0.0 to 200.0
JIS' 89 J Pt100 48 P50 -200.0 to +500.0 -300 to +900
49 P46 -200.0 to +200.0 -300 to +400
50 P32 -100.0 to +150.0 -150.0 to +300.0
51 P36 -50.0 to +200.0 -50.0 to +400.0
52 P38 -60.0 to +40.0 -76.0 to +104.0
53 P33 -40.0 to +60.0 -40.0 to +140.0
54 P05 0.0 to 500.0 0.0 to 900.0
55 P03 0.0 to 300.0 0.0 to 500.0
56 P01 0.00 to 100.00 0.0 to 200.0
dc current, dc voltage
Input Format Range No. Code Range (programmable)
4 to 20mA 64 C01
-1999 to +9999
0 to 20mA 65 C08
0 to 10mA 66 M01
-10 to +10mV 67 L02
0 to 100mV 68 L01
0 to 1V 69 L04
-1 to +1V 70 L08
1 to 5V 71 V01
0 to 5V 72 L05
0 to 10 V 73 L07

Table of Contents