8-21
Chapter 8. PROGRAM SETUP
8 - 3 General Reset
AgeneralresetcanbeexecutedwhentheDCP31isintheREADYAUTOmodeinthebasicdis-
playstate.IftheDCP31isnotinthebasicdisplaystate,press
DISP
.
A“generalreset”involvesthefollowingoperations:
•ClearingallprogramsetupsforprogramNos.1to19
•Returningparametersetupstotheirfactorysettings
•ChangingthemodetotheprogramoperationREADYAUTOmode
Operation
(1) SettheDCP31totheREADYAUTOmode.
Setvariableparameter
LOC
and
PRTC
to0.
(2) Ifyoupress
FUNC
+
CLR
+
DISP
inthebasicdisplaystate,the
displaychangestoconfirmexecutionofgeneralreset,and
G.RES
”isdisplayedontheupperdisplay.
(3) Ifyoupress
ENT
,thegeneralresetisexecuted,andoperation
startsfromstartupatpowerON.
Ifyoupress
DISP
,generalresetisnotexecuted,andtheDCP31
returnstothebasicdisplaystate.
Display
In the constant-value operation mode, all of the program No., segment No.
and profiles displays are cleared.
•IfaRAMbackuperroroccurswhenthepoweristurnedON,the
displaychangestoconfirmgeneralresetwithoutpressinganyof
thekeysontheconsole,and“
G.RES
”isdisplayedintheupper
display.
Ifyoupress
ENT
,thegeneralresetisexecuted.Otherkeys,how-
ever,cannotbeoperated.
•Thefollowingsetupdataitemsarenotreturnedtotheirfactory
settings.
C02
,
C03
: Savesettingvalues.
However,notethatifaRAMbackuperroroccurs
whenthepoweristurnedON,
C02
and
C03
set-
tingsbecome0.
Program No. Segment No.
Pattern
tendency
Output state of events 1 to 3, time events 1 to 5
G .R E S