8-13
Chapter 8. PROGRAM SETUP
Setting up PID set No. items
(1) Inthesettingdisplaystate,movetothePIDsetNo.itemsofthe
segmenttobesetupontheprogrammingmap.
(2) Ifyoupress
ENT
,thelowerdisplaystartsblinkingtoindicate
startofentrytotheNo.1setup.
(3) Press
, , or tosettotheNo.1setupPIDset
No.setting.
Settingrange: 0to8(nonheat/coolmodels)
0to4(heat/coolmodels)
(4) Whenyoupress
ENT
,blinkingontheupperdisplaystops.
Display
•Whensetupdata
C11
issetto1andPIDsetauto-switchingON
isselected,thePIDsetNo.itemsontheprogrammingmapare
skippedandnotdisplayed.
•On5Goutputmodels,whensetupdata
C18
issetto1and
programmerfunctionsareselected,thePIDsetNo.itemsonthe
programmingmapareskippedandnotdisplayed.
•On3Doutputmodels,whensetupdata
C45
issetto1and
3-position-proportionalcontrolisselected,thePIDsetNo.items
ontheprogrammingmapareskippedandnotdisplayed.
•Whensetupdata
C70
issetto1,thePIDsetNo.itemsonthe
programmingmapareallskippedandnotdisplayed.
•WhenthePIDsetNo.settingissetto0,thismeansthatthePID
setNo.oftheprevioussegmentiscontinued.WhenthePIDset
No.settingissetto0intheNo.1segments,thisisthesameasbe-
ingsetto1.
PID set No. setting value
Program No. Segment No.
Pattern
tendency
EV1 to EV3 and T1 to T5 all out
P I D