Azbil DCP31 - The controller does not change to MANUAL mode by pressing A;M in the basic display state; The controller does not change to AUTO mode by pressing A;M in the basic display state; Auto-tuning (AT) is not started by pressing AT in the basic display state; Auto-tuning (AT) is not canceled by pressing AT in the basic display state

Azbil DCP31
242 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9-7
Chapter 9. MAINTENANCE & TROUBLESHOOTING
The controller does not change to MANUAL mode by pressing
A/M
in the
basic display state
Cause Remedy
ON-OFF control is being carried out by 0D and
6D outputs.
Set PID set
P
setting in use to other than 0.0 and switch
to PID control from ON-OFF control.
3-position-proportional control is selected by 3D
output.
Set setup data
C
4
5
setting to 0 and switch to PID con-
trol from 3-position-proportional control.
Key lock is enabled. Set variable parameter
L
O
C
setting to 0 to 2.
The controller does not change to AUTO mode by pressing
A/M
in the
basic display state
Cause Remedy
Key lock is enabled. Set variable parameter
L
O
C
setting to 0 to 2.
Auto-tuning (AT) is not started by pressing
AT
in the basic display state
Cause Remedy
The controller is in the READY mode.
Press
RUN/HOLD
to set the controller to the RUN mode.
The controller is in the MANUAL mode.
Press
A/M
t o set the controller to the AUTO mode.
Input 1 over-range Correctly wire input 1 to correct input state.
Controller set not to execute AT. Set variable parameter
A
T
setting to other than 0.
The controller is set to programmer functions by
5G output.
Set setup data
C
1
8
setting to 0.
This is a heat/cool model. AT cannot be executed by 3D and 5K outputs.
Key lock is enabled. Set variable parameter
L
O
C
setting to 0 to 2.
Auto-tuning (AT) is not canceled by pressing
AT
in the basic display
state
Cause Remedy
Key lock is enabled. Set variable parameter
L
O
C
setting to 0 to 2.
Setting group other than
P
A
R
A
is not displayed by pressing
PARA
by
selecting the setting group in parameter set state
Cause Remedy
Key lock is enabled. Set variable parameter
L
O
C
setting to 0, 1 or 3.