Loading...
5-18
Chapter 5. FUNCTIONS
Mode transition
During program operation
Thesolidlinesinthebelowdiagramshowmodetransitionopera-
tions.Thebrokenlinesshowendofoperation.
Note
•
WhenshiftingbetweentheAUTOandMANUALmodes,the
modesinthesquareframescanbeshiftedbetween.
•
SelectionoftheREADYorENDmodesatendofoperationisset
upinthesetupdata.
During constant-value operation
Thesolidlinesinthefollowingdiagramshowsmodetransition
operation:
Note
WhenshiftingbetweentheAUTOandMANUALmodes,themodes
inthesquareframescanbeshiftedbetween.
Switching between program operation and constant-value operation
IntheREADYmode,selectoperationbytheconstant-valueopera-
tiondata“
.ODE”operationmodeitem.
0:Programoperation
1:Constant-valueoperation
END AUTO
END MANUAL
READY AUTO
READY MANUAL
RUN AUTO
RUN MANUAL
HOLD AUTO
HOLD MANUAL
FAST AUTO
FAST MANUAL
RESET
HOLD
RUN
FAST FAST
RUN
RESET
RUN
RESET
HOLD
ADV
ADVADVADV
RESET
Mode changes to READY or END at end of operation.
READY AUTO
READY MANUAL
RUN AUTO
RUN MANUAL
RUN
RESET